Wireless receiver

RF Rx - 4S 48V


  • sWave® wireless technology (SW868/SW915/SW917/SW922)

  • 4 potential-free optocoupler outputs

  • Transmitter/receiver assignment by teaching mode

  • LEDs for indication of switching state

Notes
  • External antenna always required for optimum wireless range

Technical data

Applied standards

EN 60947-5-1, EN 61000-6-2, EN 61000-6-3, EN 61000-4-4, EN 61000-4-5, EN 61000-4-6, EN 60068-2-6, EN 60068-2-27, EN 301 489-1, EN 301 489-3, EN 300 220-1, EN 300 220-2

Enclosure

thermoplastic, glass-fibre reinforced, shockproof, self-extinguishing UL 94 V-0

Degree of protection

IP20 (IEC/EN 60529)

Number of channels

4

Mounting

DIN rail mounting

Connection

screw connection terminals 0.14 mm² - 2,5 mm², stripping length 8 mm

Inputs

2 additional push buttons (SEL, LRN)

Outputs

4 potential-free normally open contacts (optoelectronic photo relays)

Rated operating voltage range UB

12...48 VDC (-10 % ... +25 %, abs. max. 60 V)

Rated operating current Ie

48 VDC: max. 16 mA
24 VDC: max. 21 mA

Current absorption

at 48 VDC:
typ. 1.9 mA (standby current)
typ. 8 mA (1 output switched)
typ. 8 mA (2 outputs switched)
typ. 9 mA (3 outputs switched)
typ. 10 mA (4 outputs switched)

Rated operating voltage Ue

48 VDC

Rated operating current/voltage Ie/Ue

output contacts: 0.5 A / 48 VDC (abs. max. 60 V)

Utilisation category

DC-13

Wireless range

SW868/915/917:
max. 700 m outdoors,
max. 50 m indoors
SW922:
max. 230 m outdoors,
max. 25 m indoors

Display

green LED: ready for operation,
orange LED: signalling of switching state

Operation cycles

max. 12000 telegrams with repetitions/h; SW922: max. 1440 telegrams/h

Degree of pollution

2

Ambient temperature

0 °C … +55 °C

Storage and shipping temperature

–25 °C … +85 °C

Note

Inductive loads (contactors, relays etc.) are to be suppressed by suitable circuitry.
Switching contacts are not suitable for capacitive loads.

Wireless approvals

Europe: RED 2014/53/EU
USA: FCC - XK5-RFRXSW915
Canada: IC - 5158A-RFRXSW915
Mexico: IFT - RCPSTRF17-1886
Brazil: ANATEL 04172-18-06718
Japan: ? ARIB STD-T108: 204-610002

Downloads

Loading...
Mounting and wiring instructions – RF Rx-4S 48V

German, English, French, Italian, Portuguese, Russian

PDF 2 MB 27.09.2023
Please go to the relevant product pages for additional downloads.