BZ 16 IP69K Extreme
Features/Options
- Thermoplastic enclosure
- Long life
- Differential inputs: Induction/Hall sensor operating principle
- Internal monitoring, high manipulation protection
- Potential-free outputs
- 1 NC/1 NO contact or 2 NC contacts
- Available with 3 different actuating planes:
actuating from the top "D",
actuating from the bottom "U",
actuating from the front "V".
Please indicate the desired actuating plane when ordering. - Switching capacity sao 10 mm,
sar 20 mm - Wiring compartment
- Version with higher degree of protection IP 69K: suitable for cleaning with 80 °C hot water at 100 bar pressure at a distance of 100 mm from different directions
Notes
- 1 cable gland M20x1.5 - IP 69K included in delivery
- The actuator is not included in the delivery of the switches
Product image

Technical data
| Standards | EN 61000-6-1, -2, -3, -4; EN 60947-5-2; EN 60947-5-3/PDF-M*; EN 954-1; EN 1088; EN ISO 13849-1; DIN EN 62061; 2004/108/EG |
|---|---|
| Enclosure | glass-fibre reinforced thermoplastic, self-extinguishing |
| Defined object | actuator BZ 16-B1 (order no. 90570007) non-flush mounting |
| Switching distance | switch-on distance sao = 10 mm, switch-off distance sar = 20 mm (When no ferromagnetic material is present in the vicinity of the sensor or actuator. Minimum distance |
| Hysteresis | approx. 6 mm |
| Sideways tolerance | ≤ 3 mm |
| Repeatability | < 1 mm |
| Safety-relevant data: | |
| EN 954-1 | Category 4 * |
| EN ISO 13849-1 | PL e |
| TM | max. 20 years |
| MTTFd | 57.8 years |
| DIN EN 62061 | SIL CL 3 |
| PFHD | ≥ 3 x 10-8 |
| Ie/Ue | 160 mA/24 VDC ± 15 % (reverse voltage protected) |
| Residual current | ≤ 70 mA |
| Max. fuse rating Ue | 0.25 A (slow blow) |
| Outputs | 2 enabling paths (2 NC or 1 NO/1 NC) |
| Switching voltage | max. 250 VAC |
| Cond. short-circuit current | 100 A |
| Voltage drop | refer to contact resistance |
| Max. fuse rating | 4 A (gL/gG) incoming series-connected |
| Utilisation category | AC-15; DC-13 |
| Ie/Ue of output contacts | 3 A/230 VAC; 4 A/24 VDC |
| Ui | 250 VAC |
| Overvoltage category | III |
| Degree of pollution | 3 |
| Uimp | 4 kV |
| Max. switching frequency | 1 Hz |
| Risk time | < 200 ms |
| Degree of protection | IP 69K to DIN 40050-9 |
| Ambient temperature | 0 °C … +55 °C |
| Mechanical life | 50 mio. operations |
| Contacts | AgSnO self-cleaning, positive-guided |
| Contact resistance | 100 mΩ in new condition |
| Connection | cable entry M20 x 1.5, terminal space with self-lifting clamps for max. 2 x 1.5 mm² (incl. conductor ferrules) |
| Approvals | ![]() |
* is only achieved in combination with a safety module | |