ES 14 -40°C Extreme

Features/Options

  • Cold-resistant down to -40 °C
  • Thermoplastic enclosure
  • Double insulated
  • Mounting hole diameter 22.5 mm
  • Mounting details to EN 50047
  • With pre-wired cable, cable length 2 m
  • N.B.: Please state required approvals for Russia, China and North America with your order!

Technical data

StandardsEN ISO 13849-1; EN 60947-5-1
Enclosureglass-fibre reinforced, shock-proof thermoplastic (PA 66), self-extinguishing UL 94-V0
Degree of protectionIP 65 to IEC/EN 60529
Contact materialsilver
Switching systemslow action, positive break NC contacts
Switching elements2 NC contacts, type Zb
Connectioncable 4 x AWG 20
Cable cross-section4 x 0.56 mm²
B10d (10 % Load)60 000
TMmax. 20 years
Uimp4 kV
Ui250 V
Ithe6 A
Ie/Ue6 A/250 VAC; 0.25 A/230 VDC
Utilisation categoryAC-15; DC-13
Max. fuse rating6 A gG/gN fuse
Ambient temperature–40 °C … +65 °C
Mechanical life> 30 000 operations
Operation cycles1800/h
Contact openingmax. 2 x 4 mm
Approvals

Stock types

Ordering details

Emergency-stop push-button QRUV

Type   Material no.
ES 14 QRUV 2Ö 2m -40°C...+65°C Extreme
1264315