Ex 61 Z / ExM 61 Z

Features/Options

  • Ex zone 1 and 21
  • Metal enclosure
  • Wall mounting
  • Slow or snap action: 2 contacts
  • Various spring force variants (actuating forces)
  • Pull-wire function
  • Special version only for dust Ex zone 22 available
  • N.B.: Please state required approvals for Russia, China, Brazil and North America with your order!

Product image

 

Technical data

Standards EN 60947-5-1; EN 1088;
EN 60079-0, EN 60079-1,
EN 60079-31; EN ISO 13849-1
Enclosure aluminium die-cast, enamel finish
Cover steel, enamel finish
Switch insert Ex 14, ExM 14
Degree of protection IP 65 to IEC/EN 60529
Contact material silver
Switching system slow or snap action, positive break
NC contact Zwangsöffnung
Switching elements ExM 61: change-over contact
Form C,
Ex 61: change-over with double break Zb,
galvanically separated contact bridges
Connection cable H05VV-F
Cable section 4 x 0,75 mm2
Cable length 3 m
B10d (10 % load) Ex 61 Z: 2 million
TM max. 20 years
Uimp 4 kV
Ui 250 V
Ithe T6: 6 A; T5: 3 A
Ie/Ue 6 A/250 VAC; 0,25 A/230 VDC
Utilisation category AC-15, DC-13
Max. fuse rating 6 A gL/gG D-fuse
Ambient temperature T6: –20 °C … +65 ºC;
T5: –20 °C … +95 ºC
Mechanical life > 1 million operations
Switching frequency 1800/h
Repeat accuracy ± 0,1 mm
Contact gap max. 2 x 4.5 mm
Ex certification EEx geprüft II 2G Ex d IIC T6/T5 Gb,
EEx geprüft II 2D Ex tb IIIC
T80°C/T95°C Db
IECEx Ex d IIC T6/T5 Gb,
Ex tb IIIC T80°C/T95°C Db
Approvals Ex 61: PTB 03 ATEX 1070 X;
IECEx PTB 06.0098X
(referring to the switch insert)


ExM 61: PTB 03 ATEX 1069 X (referring to the switch insert)