Ex AD
Features/Options
- Ex zone 1 and 21
- Polyester resin enclosure
- Different variants as junction or terminal boxes available
- Method of protection either increased safety "e" or intrinsic safety "i" possible
- 3 different enclosure sizes
85 x 85 mm; 115 x 115 mm; 145 x 145 mm
Product image

Technical data
| Standards | EN 60079-0; EN 60079-7; EN 60079-11; EN 60079-18; EN 61241-0; EN 61241-1 |
|---|---|
| Enclosure | glass-fibre reinforced polyester resin |
| Degree of protection | IP 66 to IEC/EN 60529 |
| Connection | hood-type or terminal blocks |
| Cable section | Ex AD 85 MK: max. 4 mm², Ex AD 115 MK: max. 6 mm², Ex AD 145 MK: max. 10 mm² (incl. conductor ferrules), single-wire |
| Cable entry | max. 8 cable entries M20 x 1.5, M25 x 1.5 or M32 x 1.5 |
| Ue | Ex AD FK: with fuse max. 250 or 550 V; Ex AD 85 FK: max. 550 V without fuse, Ex AD 115 FK, Ex AD 145 FK: max. 750 V without fuse; Ex AD … MK: max. 1100 V without fuse, max. 550 V with fuse |
| Ie/Ue | Ex AD 85: 25 A / 550 VAC, Ex AD 115: 32 A / 750 VAC, Ex AD 145: 44 A / 750 VAC |
| Temperature class | T6 / T5 / T4 |
| Ambient temperature | Ex e: T6: –40 °C … +40 °C, T5: –40 °C … +55 °C, T4: –40 °C … +60 °C; Ex i: –40 °C … +75 °C, –50 °C with special cable glands |
| Ex marking Ex AD e: | II 2G Ex em II T6, T5, T4 II 2D Ex tD A21 IP66T80 °C, T95 °C, T130 °C |
| Ex marking Ex AD i: | II 2G Ex ia/ib IIA, IIB, IICT6,T5 II 2D Ex tD A21 IP66T80 °C, T95 °C, T130 °C |
| Approvals | PTB 10 ATEX 1019 X, IECEx in 2013 |





II 2G Ex em II T6, T5, T4