// EXPLOSION PROTECTION

EEx IS M30 B

Technical data

Standards IEC 60947-5-2; EN 50014; EN 50020;
EN 50284; EN 50281-1-1
Enclosure brass-nickel, PA
Nuts 2, brass-nickel
Switching system 3-wire DC; 3D version: Namur
per DIN EN 60947-5-6
Termination 2 m pre-wired cable PVC 2 x 0.5 mm2,
3D version: plug-in connector M12 x 1, 4-pole
Protection class IP 67
Switching distance sn EEx IS M30 b: 10 mm,
EEx IS M30 nb: 15 mm
Switching distance in % steel St 37: 100 %, stainless steel: 70 %, brass: 50 %, copper: 45 %, aluminium: 40 %
Input power Pi max. 50 mW
Input voltage Ui max. 12.6 VDC
Input current Ii max. 15.9 mA
Tightening torque for the nuts M30x1,5: 100 Nm
Ambient temperature –25 °C … +75 °C
Ex certification EEx geprüft II 1G EEx ia IIC T6,
II 1D IP67 T100°C
Approvals TÜV 06 ATEX 553179

Features/Options

    • Version with plug-in connector M12 x 1 only approved for equipment category 3D

    Connector M12 x 1, 4-pole