| Standards | IEC/EN 60204-1, EN 60947-5-1, |
|---|---|
| Enclosure | black polycarbonate; polyamide terminal clamps, top hat section rail mounting to |
| Termination | screw terminals with + and - screws |
| Cable section | 1x 2.5 mm2/2x 1.5 mm2 strand including conductor fe |
| Protection class | Enclosure IP 40, Terminal block |
| Ue | 24 VDC ±15 % |
| Power consumption | approx. 2.5 W |
| Inputs | 1 NC/1 NO contact or 2 NC contacts 1 feedback input, 1 reset input |
| Outputs | enabling paths: positive-guided contacts, 1 transistor output as signalling contact |
| Utilisation category | AC-15; DC-13 |
| Ie/Ue enabling paths | 3 A/230 V; 2 A/24 V |
| Max. output current transistor output Ia | 20 mA |
| Max. fuse rating Ue | 2 A gL/gG D-fuse |
| Max. fuse rating Enabling paths | 6 A gL/gG D-fuse |
| Classification | stop category 0. Control category 4 |
| Dropout delay | < 20 ms |
| Mechanical life | > 50 million operations |
| LED indications | 4: operation, authorisation, inputs A and B |
| Degree of pollution | 3 to DIN VDE 0110 |
| Overvoltage category | III |
| Ambient temperature | 0 °C … +55 °C |