// CONTROL TECHNOLOGY

Position switches with safety function
ES 51

Technical data

Ordering details IEC/EN 60947-5-1
Enclosure aluminium die cast, paint finish
Protection class IP 65 to IEC/EN 60529
Contact material silver
Switching elements change-over contact with double break Zb or 2 NC contacts, galvanically separated contact bridges
Switching system ZwangsöffnungIEC 60947-5-1 slow action, positive break NC contacts
Termination plug-in connector M3
Cable section max. 1.5 mm2 (incl. conductor ferrules)
Cable entry M 16 x 1.5
Uimp 4 kV
Ui 400 V
Ithe 4 A
Utilisation category AC-15
Ie/Ue 4 A/400 VAC
Max. fuse rating 4 A gL/gG D-fuse
Mechanical life > 1 million operations
Switching frequency 3600/h
Ambient temperature –20 °C … +80 ºC
Repeat accuracy of switching points ±0.1 mm

Features/Options

  • With gold-plated contacts available on request

Connector M12 x 1, 5-pole