Note
The antenna must be mounted on a metal plate of min. 250 x 250 mm size.

| Standards | IEC 60068-2-6; IEC 60068-2-27 |
|---|---|
| Number of channels | 4 |
| Mounting | DIN rail mounting |
| Screw terminals | terminals with CAGE CLAMP |
| Protection class | IP 20 per IEC 60529 |
| Operating voltage Ue | 24 VDC -15 % … +20 % |
| Operating current Ie | max. 0.1 A |
| Inputs | radio, max. 4 transmitters |
| Outputs | 4 relay outputs: type depending 4 NO contacts: 13-14, 23-24 33-34, 43-44 |
| Load current/channel | 4 NO: 16A; 4 change-over: 8A |
| Display | green LED for control voltage, display of switching conditions |
| Switching frequency | max. 9000 telegrams at repetitions/h |
| Degree of pollution | 2 nach DIN VDE 0110 |
| Ambient temperature | 0°C ... +55°C |
| Storage and shipping temperature | -25°C ... +85°C |
| Vibration/shock resistance | per IEC 60068-2-6 and IEC 600068-2-27 |
| External antenna | always required for optimum sensing range |
| Note | inductive loads (contactors, relays etc.) are to be suppressed by suitable circuitry. |
| Ordering type | ||
|---|---|---|
| 4 NO contacts | Radio receiver 789-601 |
|
| 4 change-over contacts | Radio receiver 789-602 |