| Standards | EN ISO 13849-1; IEC/EN 60947-5-1; IEC/EN 60947-5-5; EN 418 |
|---|---|
| Enclosure | aluminium die-cast, enamel finish |
| Cover | glass-fibre reinforced, shock-proof thermoplastic, ultramid |
| Degree of protection | IP 67 to IEC/EN 60259 |
| Contact material | Silver |
| Switching elements | 2 NC/2 NO, 3 NC/1 NO or 4 NC contacts with double break |
| Switching system | slow action, positive break NC contacts ![]() |
| Connection | 2 x 4 pole terminal block |
| B10d (10% Load) | 100.000 |
| TM | 10 years |
| Cable section | max. 2.5 mm2 |
| Cable entry | 3 x M20 x 1.5 |
| Uimp | 2.5 kV |
| Ui | 250 V |
| Ithe | 2 A |
| Utilisation category | AC-15 |
| Ie/Ue | 2 A/250 VAC |
| Max. fuse rating | 2 A gL/gG D-fuse |
| Ambient temperature | –20 °C … +70 ºC |
| Mech. life | > 1 million operations |
| Indicator lamp | as option |
| Max. wire length | 75 m |
| Features | wire pull and breakage function |
| Approvals | ![]() |

ZS 80 2Ö/2S WVD72942501/ Download >
ZS 80 3Ö/1S WVD72942502/ Download >
ZS 80 4Ö WVD72942503/ Download >