// CONTROL TECHNOLOGY

Command devices
ES 14

Technical data

Standards IEC/EN 60947-5-1
Enclosure glass-fibre reinforced, shock-proof thermoplastic, self-extinguishing UL 94-V0
Protection class IP 65/67 to IEC/EN 60529
Contact material silber
Switching system slow action, positive break NC contacts Zwangsöffnung
Switching elements change-over contact with double break, galvanically separated contact bridges
Termination cable H05VV-F
Cable section 4 x 0.75 mm2
Uimp 4 kV
Ui 250 V
Ithe 6 A
Ie/Ue 6 A/250 VAC; 0,25 A/230 VDC
Utilisation category AC-15, DC-13
Max. fuse rating 6 A gL/gG D-fuse
Ambient temperature –20 °C … +75 °C
Mechanical life > 1 million operations
Switching frequency 1800/h
Contact opening 2 x 4 mm

Features/Options

  • Slow action with 2 NC contacts available
  • With gold-plated contacts available on request

Connector M12 x 1, 4-pole

Cable on side