| Standards | EN 60947-5-1 |
|---|
| Enclosure | glass-fibre reinforced polyamide |
|---|
| Actuator | series M permanent magnet |
|---|
| Degree of protection | IP 67 to IEC/EN 60529 |
|---|
| Contact material | Rhodium |
|---|
| Switching system | reed contacts |
|---|
| Switching elements | NO contact, change-over contact or bistable contact |
|---|
| Connection | pre-wired cable, PVC LiYY AWG 26 |
|---|
| Cable section | 1S: 2 x 0.14 mm², 1W: 3 x 0.14 mm² |
|---|
| Cable length | 1, 2 or 5 m |
|---|
| Switching voltage | 1S: max. 250 VDC, 1W: max. 120 VAC/175 VDC |
|---|
| Switching current | 1S: max. 1 A, 1W: max. 0.25 A |
|---|
| Switching capacity | 1S: max. 15 W, 1W: max. 3 W |
|---|
| Switching frequency | max. 200 Hz |
|---|
| Ambient temperature | –10 °C … +80 °C |
|---|
| Mechanical life | 109 operations |
|---|
| Electrical life | 109 operations |
|---|
| Repeatability | ± 0.02 mm |
|---|
| Resistance to vibrations | 20 g |
|---|